Description
EARTH LEAKAGE MONITOR
Description
The SE-704 is a microprocessor-based ground-fault relay for resistance-
and solidly-grounded systems. It offers very sensitive ground-fault
detection as low as 10 mA and can be used on systems with
significant harmonic content. The output contacts can be connected for
use in protective tripping circuits (such as for marina or boatyard feeder
circuits) or in alarm indication circuits. The analog output can be used
with a PLC or a meter. The SE-704 can be integrated with a shunt trip
circuit breaker to meet CE code C22.1-21 Section 78-052(2) and NEC
article 555.35(A)(1), 555.35(3), and 555.53 for marina applications